NEC editionsCalculated per NEC 2023Calculated per NEC 2026

What changed in dwelling load calculations between NEC 2023 and NEC 2026?

NEC 2026 moved the dwelling calculations from Article 220 to Article 120 and changed four things that show up in the numbers. On a 2,200 ft² all-electric house with a 48 A EV charger, the standard method falls from 201.2 A (NEC 2023) to 185.4 A (NEC 2026): the general lighting load drops from 3 to 2 VA per square foot and the 125% continuous-load adder (2,880 VA here) no longer applies in load calculations. The optional method moves the other way, from 119.5 A to 141.1 A, because the first tier shrinks from 10,000 to 8,000 VA and the EV charger is taken at 100% outside the tiers instead of at 40% inside them. Which edition applies is set by your jurisdiction’s adoption, not by the calendar.

Updated September 23, 2026. Numbers on this page are computed by the same engine as the calculators, under NEC 2023 and NEC 2026.

Worked example: standard method, NEC 2023 and NEC 2026 on the same house

Calculated per NEC 2026

Standard method (Article 220 Part III) and Standard method (Article 120 Part III)

Inputs

NEC editionCalculated under both 2023 and 2026
Floor area2,200 ft² plus 440 ft² attached garage
Small-appliance circuits2
Laundry circuits1
CookingElectric range 12 kW
Clothes dryer5,000 VA
Appliances fastened in placeElectric water heater 4,500 VA; Dishwasher 1,200 VA; Garbage disposal 900 VA
HeatingElectric resistance 8,000 VA in 4 units
Air conditioning4,200 VA
EV chargingEV charger, 48 A at 240 V 11,520 VA

Result

NEC 2023 standard201.2 A48,297 VA; 225 A minimum
NEC 2026 standard185.4 A44,493 VA; 200 A minimum
Change-15.9 Alighting 7,920 VA → 5,280 VA; continuous adder 2,880 VA → 0
Line itemNECConnectedDemandBasis
General lighting and receptacles120.415,280 VA(in subtotal)2,200 ft² + 440 ft² attached garage (120.41) × 2 VA/ft²
Small-appliance branch circuits120.52(A)3,000 VA(in subtotal)2 circuits × 1500 VA
Laundry branch circuit120.52(B)1,500 VA(in subtotal)1 circuit × 1500 VA
General load after demand factorsTable 120.459,780 VA5,373 VA3,000 VA at 100% = 3,000 VA; 6,780 VA at 35% = 2,373 VA
Appliances fastened in place120.536,600 VA6,600 VA3 appliances at 100%
Clothes dryers120.545,000 VA5,000 VA1 × 5,000 VA (nameplate) at 100% (Table 120.54)
Cooking appliances120.5512,000 VA8,000 VAColumn C for 1 unit = 8 kW
Electric space heating120.608,000 VA8,000 VALarger of electric space heating 8,000 VA and cooling 4,200 VA; heating governs (120.60)
Air conditioning120.604,200 VA0 VAOmitted, heating is the larger noncoincident load (120.60)
Motors120.50 / 430.240 VANone
25% of largest motor120.50 / 430.240 VANo motor loads
EV supply equipment120.5711,520 VA11,520 VA1 unit at nameplate, 7,200 VA where no nameplate is available (120.57)
Other loads120.140 VANone
0% of continuous loads120.5(E)0 VA11,520 VA continuous; no 125% adder in load calculations (120.5(E))

The line items shown are the 2026 run (Article 120 numbering). Two rows differ from 2023: general lighting at 2 VA/ft² (5,280 VA instead of 7,920 VA including the garage), and a zero continuous-load row where 2023 added 2,880 VA for the charger. Together they move the minimum service from 225 A to 200 A.

  • Clause numbers follow the edition: 220.41 becomes 120.41, 220.57 becomes 120.57, and so on. The calculator and the printed report renumber automatically.

Optional method on the same house, both editions

Calculated per NEC 2026

Optional method (220.82) and Optional method (120.82)

Inputs

2023 (220.82)General load first 10,000 VA at 100%, remainder 40%; EVSE at nameplate inside the general load (220.82(B)(3)a)
2026 (120.82)General load first 8,000 VA at 100%, remainder 40%; EVSE outside the tiers at 100% of the 120.57 value (120.82(D)); attached garage counted in lighting (120.5(C))

Result

NEC 2023 optional119.5 A28,688 VA; 125 A minimum
NEC 2026 optional141.1 A33,872 VA; 150 A minimum
Change+21.6 AEVSE 11,520 VA at 40% inside the tiers → 100% outside them
Line itemNECConnectedDemandBasis
General lighting and receptacles120.82(B)(1)5,280 VA(in subtotal)2,200 ft² + 440 ft² attached garage (120.5(C)) × 2 VA/ft²
Small-appliance and laundry circuits120.82(B)(2)4,500 VA(in subtotal)3 circuits × 1500 VA
Appliances fastened in place120.82(B)(3)6,600 VA(in subtotal)3 at nameplate
Ranges, ovens and cooking units120.82(B)(3)12,000 VA(in subtotal)1 at nameplate
Clothes dryers120.82(B)(3)5,000 VA(in subtotal)1 at nameplate
Permanently connected motors120.82(B)(4)(in subtotal)None
Other fixed loads120.82(B)(3)(in subtotal)None
General load after demand factors120.82(B)33,380 VA18,152 VAFirst 8,000 VA at 100%; remaining 25,380 VA at 40% = 10,152 VA
Electric space heating at 40%120.82(C)(5)8,000 VA0 VA40% of 8,000 VA (4 separately controlled units); omitted, cooling selection is larger
Air conditioning and cooling120.82(C)(1)4,200 VA4,200 VA100% of 4,200 VA; largest selection
EV supply equipment120.82(D)11,520 VA11,520 VA1 unit at 100% of the 120.57 value (nameplate, 7,200 VA fallback), outside the general-load demand tiers (120.82(D))

Under 2023 the 11,520 VA charger sat in the general load where all of it fell in the 40% tier, costing 4,608 VA. Under 2026 it is a separate line at 100%. That, plus the smaller first tier, raises the optional result by 21.6 A even though the lighting load fell.

The four changes that move the numbers

Every other rule in the dwelling calculation carried over with a new number. These are the ones that change results:

  • General lighting and receptacle load: 3 VA/ft² (220.41) becomes 2 VA/ft² (120.41). On this house that is 2,640 VA less connected load before Table 120.45.
  • Continuous loads: 230.42(A)(1) added 25% of continuous loads to the service calculation in 2023; 120.5(E) states the 125% factor is not applied in load calculations under 2026. Branch circuits and feeders are still sized at 125% under their own articles.
  • EV supply equipment: 220.57 took the larger of 7,200 VA or nameplate; 120.57 takes nameplate when it exists, with 7,200 VA only as a fallback. Small chargers count for less.
  • Optional method: 120.82(B) starts the 40% tier at 8,000 VA instead of 10,000, counts the attached garage in the lighting load, and 120.82(D) pulls EVSE out of the general load at 100%.

Which edition to calculate under

The edition is whichever your authority having jurisdiction has adopted, often with amendments and often a cycle or two behind the current book. Calculating under the wrong one is a plan-review rejection either way, so the calculator carries an edition on every calculation, defaults to the one set in your account, and prints "Calculated per NEC 2023" or "Calculated per NEC 2026" on every page of the report.

Both editions in the calculator were verified against their code text and Annex D examples; the methodology page lists every clause and its verification status per edition.

What did not change

Table 220.45 demand factors for general lighting, 220.53 for fastened-in-place appliances, Table 220.54 for dryers, Table 220.55 and its notes for cooking, 220.60 for noncoincident heating and cooling, and 430.24 for motors all carry into Article 120 with the same values. The neutral calculation (220.61 → 120.61) is likewise unchanged in substance.

Frequently asked questions

Did the standard method get easier and the optional method harder?
On houses with an EV charger, broadly yes. Here the standard method dropped 15.9 A and the optional method rose 21.6 A. On a house without EVSE the optional method changes only through the 8,000 VA first tier and the lighting load, and can move either way.
Do I still size the EV branch circuit at 125%?
Yes. 625.41 and 210.20 still require the branch circuit and its overcurrent device to be rated for 125% of the continuous load. 120.5(E) only removes the adder from the load calculation for the feeder or service.
Does 2 VA/ft² apply to the existing-dwelling method too?
Yes; 120.83 uses the 120.41 lighting load. It also replaces the 2023 method’s two paths (A) and (B) with a single set of tiers that puts added EVSE at 80% and added central electric heating at 80%.
Can I run both editions on one saved calculation?
Yes. The edition selector on the Pro load calculator recalculates the same inputs under either edition, and the report states which one it was issued under.

Related questions

More for electricians: NEC 2023 load calculations you can hand to an inspector · all answers

Inspector/Reviewer Note. Informational estimate only — not a compliance document. Verify all calculations against the NEC edition adopted in your jurisdiction. Calculated per NEC 2023. Calculated per NEC 2026. Nameplate ratings in the examples are typical values; your equipment will differ. Read the methodology for the clauses implemented and their verification.